Spring principle. If the pressure is below the set value, the microswitch (2) is operated. When pressure builds up, the piston works (6) against the spring plate (5). This is supported on the continuously adjustable compression spring (4) away. When the set pressure is reached the nozzle (7), the piston (6) transmits the force on the spring plate (5) whereby the Microswitch (2) released and on electrical signal is triggered. The to monitoring pressure is provided by the Preload of the spring (4) is determined. The Adjustment is made by turning the Adjusting element (3). A turn against the clock hand, lowers the switching pressure. One Clockwise rotation increases switching pressure. The adjusting element (3) is determined by the locking screw or the fixing cover. A mechanical stop prevents the compression spring (4) from turning open.